Y49-23KVL

keyword 2-pole threaded DC discharge starting voltage 23000V
Product Info Product name: Y49-23KVL
Item code: 11042084

Mounted between the neutral line and ground of the communication circuit board and power supply circuit of the 2-pole arrester (GDT) communication device, and used to protect the device from induced voltage and TOV (temporary overvoltage) induced in the line to do.

Compared to other products, it has a very large current capacity (8 / 20µs, 80kA).

Main applications

  • Various electronic devices
  • Communication line protection
  • AC power supplies
  • Inverters
  • Very large current withstand capability
  • Low capacitance
  • Broadband compatible
  • Excellent heat and mechanical shock due to use of ceramic envelope
  • Excellent current withstand capability and temperature environment characteristics of repeated surge
Dimensions  (Unit: mm)
Specification
item conditions Performance
DC discharge start voltage 5 kV / s 20 to 25 kV (AC 14.2 to 17.7 kV)
Insulation resistance DC 1000 V 10000 MΩ or more
Impulse discharge start voltage 1.2 / 50 μs, 30 kV 30 kV or less
Maximum impulse current capability 8/20 μs 80 kA
mass - Approx. 300 g
Notes on use

When using this product for AC power, be sure to use it together with a varistor.

If the arrester is used alone, a follow current may occur.

We also have AV series (2 poles) and AV3P series (3 poles) with arresters and varistors integrated.