ZP series
IEC Category C2/D1 compliant
Conforming standards
- IEC 61643-21 compliant
- RoHS compliant
Features
- Slim design enables space saving
- Plug-in type (circuit not broken by inserting or removing plug)
- DIN rail mountable (35mm)
- Special tester (ZPT1 type) can be used to detect deterioration.
- Round type crimped terminal for M4 (N type)
External view
Applications / Characteristics
Item | Performance | |||||
ZP-A1 | ZP-DC24 | ZP-DC48 | ZP-H2-H1 | ZP-N1 ZP-N1JKN |
||
Applications | Telephone line, ISDN line, ASDL Line | DC 24V signal line, control circuit | DC 48V signal line, control circuit | RS422, RS485 | Balanced circuit, wind speed meter, pyranometer, rain gauge, hygrometer | |
Maximum continuous operating voltage (Uc) | DC170V | DC27V | DC25V | DC5V | DC150V | |
Rated current | DC100mA | DC3A | DC100mA | DC3A | ||
Series resistance | 10Ω or less | - | 5Ω±10% | - | ||
Voltage protection level (Up) | 1.0 kV or less | 500V or less | 50V or less | 1.0 kV or less (to ground) 50V or less (inter line) *ln case of balanced circuit |
||
Impulse durability (two lines together) | category C2 (8/20 μs) | 10 kA (10 time) | 4kA (10 time) | 10kA (10 time) | 4kA (10 time) | |
category D1 (10/350 μs) | 2.5 kA (2 time) | 1kA (2 time) | 5kA (2 time) | 1kA (2 time) | ||
Operating enviromental conditions | Rated operating temperature Rate operating himidity | -40 °C to +70 °C 96% or less (no condensation) |
||||
Wiring method | Relay wiring (O), Suspended wiring (X) | Relay wiring (O), Suspended wiring (O) | Relay wiring (O), Suspended wiring (X) | Relay wiring (O), Suspended wiring (O) |
Item | Performance | |||||
ZP-NM ZP-NMJKN |
ZP-EN-1 ZP-EN1JKN |
ZP-EN3 ZP-EN3JKN |
ZP-K2 ZP-K2JKN |
ZP-H3(06,12,24,48V) ZP-H3 24V JKN |
||
Applications | Multi-core measurement line, disaster prevention monitoring board (multi-core), wind speed meter, platinum thermometer | Telephone line, ISDN line, ASDL Line | ISDN, xDSL, digital leased lind | AC/DC 110V control circuit, relay circuit, speaker line | Instrumentation line, potentiometer, slow pulse, DC 4-20mA, RS232C, RS422, RS485 | |
Maximum continuous operating voltage (Uc) | DC150V | DC170V | DC52V | DC180V AC140V |
DC9V(06V), DC13.5V(12V), DC27V(24V), DC52V(48V) | |
Rated current | - | DC100mA | DC3A | DC400mA(06v), dc100Ma(12, 24, 48v) | ||
Series resistance | - | 10Ω or less | - | 5Ω±10% | ||
Voltage protection level (Up) | 1.0 kV or less (to ground) 50V or less (inter line) |
400V or less | 200V or less | 800V or less | 800 V or less (06V), 100V or less (12V), 120V or less (24V), 140V or less (48V) |
|
Impulse durability (two lines together) | category C2 (8/20 μs) | 4 kA (10 time) | 10 kA (10 time) | 4 kA (10 time) | 10 kA (10 time) | |
category D1 (10/350 μs) | 1 kA (2 time) | 2.5kA (2 time) | 1kA (2 time) | 5kA (2 time) | ||
Operating enviromental conditions | Rated operating temperature Rate operating himidity | 40 °C to +70 °C 96% or less (no condensation) |
||||
Wiring method | Relay wiring (X), Suspended wiring (O) | Relay wiring (O), Suspended wiring (X) | Relay wiring (O), Suspended wiring (O) | Relay wiring (O), Suspended wiring (X) |