MZEV3-200
SPD for low-voltage power supply AC 100V series or AC
230V series, Three-phase 4-wire
Conforming standards
- IEC 61643-11 compliant
- RoHS compliant
Features
- For the protection of low-voltage power supply equipment
- Small size and space-saving installation in the device,
- Screw fixing product
- One unit can protect both lines and ground at the same time
- Equipped with a deterioration diagnosis function and a detachment mechanism
Application
- EV Charging devices,
- Lighting panels
Specification
| Test Standards | ー | IEC 61643-11:2011 / JIS C 5381-11:2014 |
| Test Classification | ー | Class II, III |
| Rated operating voltage | ー | AC 240 / 120 V |
| Maximum continuous working voltage UC | L-to-L, L-to-PE | AC 275 V |
| Open Circuit Voltage UOC | 1.2/50 μs | 5 kV |
| Voltage protection level UP | L-to-PE | ≤ 1.35 kV |
| Overcurrent protection | MCCB:50AF / 50AT | |
| Rated Short-Circuit Current ISCCR | L-to-PE | AC 5 kA |
| Transient overvoltage characteristic UT | L-to-PE | AC 335 V, 5s |
| Leakage current IPE | L-PE to 255 V AC | ≤ 1 mA |
| Nominal Discharge Current In | 8/20 μs | 2.5 kA [1 wire] |
| Maximum Discharge Current Imax | 8/20 μs | 5 kA [1 wire] |
| Voltage Protection Rating VPR | ≤ 1.2 kV | |
| Number of Ports | 1 port | |
| Mounting method | Screw fixing | |
| Classification of protection classes | ー | IP 20 |
| Degradation indication | LED on: Normal / LED off: Deterioration (replacement required) | |
| Recommended External Separator | ー | NF50-SMU (Mitsubishi Electric) |
| mass | ー | about 56 g |
Dimensions
Document