Y20-250A

keyword 2 poles No lead wire DC discharge starting voltage 250V
Product Info Product name: Y20-250A
Item code: 11010728

Mounted between the neutral line and ground of the communication circuit board and power supply circuit of the 2-pole arrester (GDT) communication device, and used to protect the device from induced voltage and TOV (temporary overvoltage) induced in the line to do.
Compared to other products, it has a very large current capacity (8 / 20µs, maximum 80kA).

Main applications

  • Various electronic devices
  • Communication line protection
  • AC power supplies
  • Inverters
  • Very large current withstand capability
  • Low capacitance
  • Broadband compatible
  • Excellent heat and mechanical shock due to use of ceramic envelope
  • Excellent current withstand capability and temperature environment characteristics of repeated surge
Dimensions  (Unit: mm)
Specification
item conditions Performance
DC discharge start voltage 100 V / s 250 V ± 50V
Impulse discharge start voltage 10/200 μs, 3 kV 750 V or less
Insulation resistance DC 100 V 100 MΩ or more
Impulse current capacity 8/20 μs, 80 kA * Once
Impulse current capacity 8/20 μs, 60 kA * 10 times
Impulse current capacity 10/200 μs, 10 kA * Once
Maximum AC current capacity AC 100A, 1 s * Once
DC holdover voltage 10/200 μs, 200A, power supply DC200mA, voltage 80V 150 ms or less
Service life 10/200 μs, 500A 1000 times
Capacitance - 5.0 pF or less
mass - 6.5 g

 * Discharge without cracks or short circuit of electrodes in the ceramic part.

Notes on use

When using this product for AC power, be sure to use it together with a varistor.

If the arrester is used alone, a follow current may occur.

We also have AV series (2 poles) and AV3P series (3 poles) with arresters and varistors integrated.