MZS-200AV
IEC Class I/II compliant
Conforming standards
- IEC 61643-11 compliant
- RoHS compliant
Features
- MZS-200AV is a product that connects between the phase and neutral, connect MZS-NPE between the neutral and earth
- Impulse discharge current up to 25 kA (direct strike waveform 10/350 µs)
- Voltage protection level 2.0kV or less
- Deterioration display function (warning contact output terminal attached)
- DIN rail mountable (35mm)
Application
- Low voltage power supply circuits in switchboard and distribution boards (AC 100V/200V)
- Power supply circuits in control equipment (AC 100V/200V)
Characteristics
Item | Measurement conditions | Performance |
Maximum continuous operating voltage (50/60Hz)(Uc) | - | 275V |
Impulse current (limp) | 10/350µs | 25kA |
Short-circuit withstand capabillity (lsccr) | L-NPE | 50kA |
Voltage protection level (Up) | Based on IEC | 1.5 kV or less |
External view
Installation examples (MZS-200AV+MZS-NPE)