MZSR-200JK3ARI

1

IEC Class II compliant

Conforming standards

  • IEC 61643-11 compliant
  • RoHS compliant

Features

  • This products use for primary side of e leakage breaker in three-phase four-wire system
  • Maximum discharge current up to 40kA (induction light waveform 8/20µs)
  • Plug-in type
  • Deterioration display function (warning contact output terminal)
  • DIN rail mountable (35mm)

Applications

  • Low voltage power supply circuits in switchboards and distribution boards (AC 100V/200V, 400V)
  • Power supply circuits in control equipment (AC 100V/200V, 400V)

Characteristics

                                  Item Measurement conditions MZSR-200JK3ARI
Maximum continuous operating voltage (50Hz/60Hz)(Us) - AC275V
Maximum discharge current (Imax) 8/20µs 40kA
Norminal discharge current (In) 8/20µs 20kA
Voltage protection level (Up) Based on IEC

1.4kV or less (each phase)

1.5kV or less

(N-PE)

External view