MKYS4S

1

IEC ClassII compilant

Conforming standards

  • IEC 61643-1/IEC 62305-4 compilant
  • RoHS compliant

Features

  • 2-electrode dimensions, width 50mm (MKYS2series, S4 series)
  • A single unit provides protection across wire and to ground.
  • Accommodates from single-phase two-wire up to three-phase four-wire (MKY44series, S2series, S4series)
  • Deterioration display function (warning contact output terminal attached: S type)
  • Easily installed into distribution boards
  • Mountable on DIN rail, can be attached with articulated mounting plate.
  • With retractable terminal cover for electric shock prevention

Application

  • Low voltage power supply circuits in switchboards and distribution boards (AC 100V/200V, 400V)

Characteristics

Item

Measurement

conditions

MKYS4

MKYS4S

Maximum continuous operating voltagr (50/60Hz)(Uc) -

Three-phase three-wire AC 510V

Three-phase four-wire AC 510V

Maximum discharge current (Imax) 8/20µs 200 kA (inter line, to ground)
Nominal discharge current (Imax) 8/20µs 10 kA (inter line, to ground)
Voltage protection level (Up) Based on IEC

2.4 kV or less (inter line) 

2.4 kV or less (to ground)